| A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IF8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle. |
| Studio 5000 Logix Designer 30.01.00 contains an unquoted service path vulnerability in the FactoryTalk Activation Service that allows local users to potentially execute code with elevated privileges. Attackers can exploit the unquoted path in C:\Program Files (x86)\Rockwell Software\FactoryTalk Activation\ to inject malicious code that would execute with LocalSystem permissions. |
| A denial-of-service vulnerability exists via the CIP/Modbus port in the Rockwell Automation Micro850/870 (2080 -L50E/2080 -L70E). If exploited, the CIP/Modbus communication may be disrupted for short duration. |
| A security issue exists within the 5032 16pt Digital Configurable module’s web server. Intercepted session credentials can be used within a 3-minute timeout window, allowing unauthorized users to perform privileged actions. |
| A code execution security issue exists in the affected product. An attacker with physical access could abuse the maintenance menu of the controller with a crafted payload. The security issue can result in arbitrary code execution. |
| A security issue exists due to improper handling of malformed CIP packets during fuzzing. The controller enters a hard fault with solid red Fault LED and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF019. To recover, clear the fault. |
| A denial-of-service security issue in the affected product. The security issue stems from a fault occurring when a crafted CIP unconnected explicit message is sent. This can result in a major non-recoverable fault. |
| A local server-side request forgery (SSRF) security issue exists within Studio 5000® Simulation Interface™ via the API. This vulnerability allows any Windows user on the system to trigger outbound SMB requests, enabling the capture of NTLM hashes. |
| A security issue affecting multiple Cisco devices also directly impacts Stratix® 5410, 5700, and 8000 devices. This can lead to remote code execution by uploading and running malicious configurations without authentication. |
| A Local Privilege Escalation vulnerability exists in the affected product. The vulnerability requires a local, low privileged threat actor to replace certain files during update and exists due to a failure to perform proper security checks before installation. |
| A security issue exists due to the web-based debugger agent enabled on Rockwell Automation ControlLogix® Ethernet Modules. If a specific IP address is used to connect to the WDB agent, it can allow remote attackers to perform memory dumps, modify memory, and control execution flow. |
| A denial-of-service security issue exists in the affected product and version. The security issue stems from a high number of requests sent to the web server. This could result in a web server crash however; this does not impact I/O control or communication . A power cycle is required to recover and utilize the webpage. |
| A security issue exists within the 5032 16pt Digital Configurable module’s web server. The web server’s session number increments at an interval that correlates to the last two consecutive sign in session interval, making it predictable. |
| Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. |
| A memory abuse issue exists in the Rockwell Automation Arena® Simulation. A custom file can force Arena Simulation to read and write past the end of memory space. Successful use requires user action, such as opening a bad file or webpage. If used, a threat actor could execute code or disclose information. |
| A memory abuse issue exists in the Rockwell Automation Arena® Simulation. A custom file can force Arena Simulation to read and write past the end of memory space. Successful use requires user action, such as opening a bad file or webpage. If used, a threat actor could execute code or disclose information. |
| A memory abuse issue exists in the Rockwell Automation Arena® Simulation. A custom file can force Arena Simulation to read and write past the end of memory space. Successful use requires user action, such as opening a bad file or webpage. If used, a threat actor could execute code or disclose information. |
|
KEPServerEX does not properly validate certificates from clients which may allow unauthenticated users to connect.
|
| An attacker could send crafted SMTP packets to cause a denial-of-service condition where the controller enters a major non-recoverable faulted state (MNRF) in CompactLogix 5370 L1, L2, and L3 Controllers, Compact GuardLogix 5370 controllers, and Armor Compact GuardLogix 5370 Controllers Versions 20 - 30 and earlier. |
| An attacker could send a crafted HTTP/HTTPS request to render the web server unavailable and/or lead to remote code execution caused by a stack-based buffer overflow vulnerability. A cold restart is required for recovering
CompactLogix 5370 L1, L2, and L3 Controllers, Compact GuardLogix 5370 controllers, and Armor Compact GuardLogix 5370 Controllers Versions 20 - 30 and earlier. |